Permit: T06CM04823

Parcel: 112040130


Addresses:

2525 E GLENN ST

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
06/28/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
06/14/2007 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) OK TO COVER ALL EXTERIOR WALLS WITH ? EXCEPT BATHROOM
06/13/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CLIP ALL 4 X 4 POST BASES
2) H25 EVERY RAFTER
3) OVERSPAN WINDOW BARS
06/04/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/01/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ? AB 48" ON CENTER ALL BASE PLATES
2) POSITIVE CONNECTION ALL EXTERIOR WALLS FROM BAS PLATE TO RAFTERS
3) 2 WINDOWS EAST WALL 4 X 6 HEADER JOINTS OVER WINDOW
4) ELECTRIC IN WALLS NOT ON PLAN
5) AB'S EVERY PLATE JOINT 3"-12"
6) FRONT ADDITION DBL STUD AT BEAM BEARING/PONY WALL
7) COMPLY WITH HEADER SCHEDULE
8) STRAP ALL DBL TOP PLATE WITH 24" OVER LAP
9) MISSING STUDS THROUGHOUT
10) EXPOSE ALL HEADERS
11) NAIL ALL HOLES AND ALL CLIPS
04/26/2007 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
1) NOT READY PER SUPER
04/03/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
EXPOSE REAR STORAGE BIRD BOARDS TO VERIFY CLIPS
ALL BOTTOM PLATES MUST BE TREATED
REVISE PLAN TO SHOW MASONATE SIDING
NAIL SIDING 6" O.C ALL ENDS & EDGES 12" FIELD 8D
REMOVE ALL SIDING EAST WALL 1 REPAIR NORTH WALL
ALL JOINTS NEED STUDS
COMPLY WITH OPENING SCHEDULE FRONT WINDOW
03/27/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OWNER WISHES TO DISCUSS PROJECT WITH MR. CAMACHO
03/26/2007 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
03/23/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CHECK NAILING ALL MASONITE SIDING