Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/30/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NEW CKT "MPR 21" IN OFFICE NOT PROPERLY IDENTIFIED IN PANEL DIRECTORY. PANEL DIRECTORY TO BE CORRECT LEGIBLE AND SECURE TO INNER COVER -- NEC 408.4 WILL NEED TO PAY REINSPECTION FEE PRIOR TO FINAL APPROVAL IF NOT CORRECT NEXT INSPECTION. |
|
| 01/24/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RINGS 314.20 2. PROVIDE A LETTER FROM ENGINEER FOR DELATION OF SWITCHES. 3. REVISE PANEL SCHEDULE |