Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T06CM04806
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Partial Approval
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/18/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK POLE BASE NORTH OF 2018 |
|
| 04/10/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK AREA LTG. BLDG. #1 THRU #5 |
|
| 02/14/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK TO POUR FIRST POLE BASE EAST OF POOL |
|
| 12/19/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* - OK RACEWAYS ACROSS ROAD PANEL "LD" (STUB TO ACROSS ROAD) - OK SITE LIGHTING RACEWAY BETWEEN BUILDING #3 & 5 *NOTE: ALL TEMPORARY CONSTRUCTION POWER IS TO BE PERMITTED AND INSPECTED BEFORE ENERGIZED. |
|
| 12/10/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : 1. RACEWAYS TO BE EXPOSED FOR INSPECTION, TRENCH FULL OF DIRT & WATER 2. RACEWAYS TO BE MINIMUM 24" DEEP IN TRAFFIC AREAS, 18" ALL OTHERS 3. FIRE ALARM WIRING TO BE IN SEPARATE RACEWAYS THAN POWER AND LIGHT CONDUCTORS 4. WHEN INSPECTION IS CALLED IN, LEAVE A MESSAGE FOR WHAT AND WHERE INSPECTION IS NEEDED AND HAVE PLANS AVAILABLE AT INSPECTION LOCATION. |
|
| 03/15/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) NEED PROPER ? BLANK |
|
| 03/13/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK FEEDER RACEWAY S.E SUB PANEL PARKING AREA |
|
| 02/21/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK SITE UNDERGROUND COVER AROUND FIRST BUILDING PLANTER AREAS ETC. EXCEPT INTO PANEL (LIGHTING RACEWAYS) |
|
| 12/11/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* PHASE 1 AREA UNDER ASPHALT (RACEWAYS FOR SUB-PANELS AND SITE LIGHTING) POLE BASES NOT IN @ THIS TIME. |
|
| 12/07/2006 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* NEED 24" DEPTH, HAVE MORE COMPLETE FOR INSPECTION |