Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL |
|
| 12/06/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* MARK UNIT DATA PLATES WITH PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. #10 WIRE ONLY GOOD UP TO 30 AMP. SECURE CONDUIT ON ROOF. PERMANENTLY I.D UNITS WITH ADDRESS & UNIT NUMBER. |