Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/07/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEUTRAL BUSSES GROUNDED 2. FINISH PREVIOUS ITEMS 1, 2, 7 & 8 |
|
| 12/06/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SEPARATE GROUNDS AND NEUTRALS AT SUB-PANELS 2. CLEAN FOREIGN MATERIAL FROM BUSS 110.12 AND EXCESS DIRT OUT OF BOTTOM OF PANELS. 3. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING. 4. BREAKER TO BE LISTED FOR USE BY MANUFACTURER 5. NEED DISCONNECTING MEANS FOR INSTA-HOT 6. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 7. PROTECT CONDUCTORS FROM SHARP METAL EDGES. 8. PLEASE PROVIDE LETTER FOR LIGHT FIXTURE -- NOT AS PLANS |