Permit: T06CM04802

Parcel: 134161990


Addresses:

7431 E 22ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM04802

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/08/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/07/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NEUTRAL BUSSES GROUNDED
2. FINISH PREVIOUS ITEMS 1, 2, 7 & 8
12/06/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. SEPARATE GROUNDS AND NEUTRALS AT SUB-PANELS
2. CLEAN FOREIGN MATERIAL FROM BUSS 110.12 AND EXCESS DIRT OUT OF BOTTOM OF PANELS.
3. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING.
4. BREAKER TO BE LISTED FOR USE BY MANUFACTURER
5. NEED DISCONNECTING MEANS FOR INSTA-HOT
6. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
7. PROTECT CONDUCTORS FROM SHARP METAL EDGES.
8. PLEASE PROVIDE LETTER FOR LIGHT FIXTURE -- NOT AS PLANS