Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM04802
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/08/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
12/06/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
11/30/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. FINISH ROOM 114 * BOXES MORE THAN 1/4" FROM BOX TO SURFACE WILL NEED AN APPROVED EXTENDER RING 314.20 |
|
11/29/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. WE HAVE OVERFILL AT BOXES. 2. FILL UNUSED OPENINGS AT BOXES 3. SUPPORT VDV CABELING 725.3 & 6 800.3 & 6 OK TO TILE EXCEPT AS NOTED. |
|
11/27/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO COVER CEILING IN SPACE 7431 SPACE 7435 NOT READY |
|
11/22/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CLEAN SUB PANEL TEXTURE SPRAYED INTO PANEL 2) SCREW LAY IN FIXTURES TO GRID 3) GET RID OF UNUSED WIRING IN CEILING OR PROPERLY SUPPORT 4) SEAL OPEN K.O.'S IN PANELS |
|
11/06/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 02035 -- ELEC. INTERMEDIATE SECURE ALL CONDUITS AT PANEL |