Permit: T06CM04796

Parcel: 12602016B


Addresses:

4639 E 1ST ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
11/15/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
10/30/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1. IT IS NOT INSTALLED PER PLAN.
GAS PIPING IS SIZED BY DEVELOPED LENGTH AND TOTAL BTU CONSUMPTION. PROVIDE AN ACCURATE PLAN AND INSTALL ACCORDINGLY.
2. DO NOT SUPPORT PIPE BY PARAPET.
3. SUPPORT PIPING PER TABLE 3-1 2003 UPC