Permit: T06CM04796

Parcel: 12602016B


Addresses:

4639 E 1ST ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/14/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/22/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CONTRACTORS SCOPE OF WORK IS COMPLETE
2) JIM JASTER IS WORKING ON NEW PERMIT FOR OTHER WORK
11/21/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. TIGHTEN LOOSE SEAL TITE FITTINGS
2. LABEL DISCONNECTS
3. NEED REJECTION PINS AT SERVICE DISCONNECTS.

* TENANT TO VERIFY PERMITS FOR OTHER WORK.
11/17/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. GROUND JUNCTION BOXES 250.148
2. PROVIDE REJECTION PINS AT SERVICE DISCONNECTS.
3. INSTALL ALL STRANDS UNDER LUGS.
4. SEPARATE GROUNDS AND NEUTRALS AT PANEL "2"
5. A SEALING DEVICE IS NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS.
6. USE APPROVED FITTINGS WITH LB
7. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 408.6
8. SECURE CONDUITS AS PER CODE.
9. PLEASE PROVIDE ACCESS TO ROOF
11/16/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
11/15/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
LOCKED NO ANSWER AT DOOR