Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/22/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CONTRACTORS SCOPE OF WORK IS COMPLETE 2) JIM JASTER IS WORKING ON NEW PERMIT FOR OTHER WORK |
|
| 11/21/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. TIGHTEN LOOSE SEAL TITE FITTINGS 2. LABEL DISCONNECTS 3. NEED REJECTION PINS AT SERVICE DISCONNECTS. * TENANT TO VERIFY PERMITS FOR OTHER WORK. |
|
| 11/17/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. GROUND JUNCTION BOXES 250.148 2. PROVIDE REJECTION PINS AT SERVICE DISCONNECTS. 3. INSTALL ALL STRANDS UNDER LUGS. 4. SEPARATE GROUNDS AND NEUTRALS AT PANEL "2" 5. A SEALING DEVICE IS NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS. 6. USE APPROVED FITTINGS WITH LB 7. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 408.6 8. SECURE CONDUITS AS PER CODE. 9. PLEASE PROVIDE ACCESS TO ROOF |
|
| 11/16/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 11/15/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* LOCKED NO ANSWER AT DOOR |