Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* OK TO CLEAR SERVICE INC ONLY 1. FOR FINAL INSTALL FUSE REJECT CLIPS 2. RE-TIE GAS BOND ONCE MECH OR PLUMB CONTRACTOR FINISHED WITH REDIRECTION. 3. ROOF ELECTRICAL WORK NOT READY - CALL FOR INSPECTION PRIOR TO ENERGIZING. 4. FINISH GRADE WORK IN FRONT OF SERVICE PRIOR TO FINAL. 1. FON FINAL INSTALL FUSE REJECT CLIPS 2. RE: TIE GAS BOND ONCE MECH OR PLUMB. CONTRACTOR FINISHED WITH REDIRECTION. 3. ROOF ELECTRICAL WORK NOT READY -- CALL FOR INSPECT |
|
| 10/25/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEW SUB-PANEL P- IS WATER LOGGED, RAIN HAS COME IN THRU TOP CONDUIT ENTRIES, CABLES, TERMINATIONS, BREAKERS, PNL BUS, GROUND TERMINATION WATERED, TOP ENTRIES TO BE MADE EFFECTIVELY SEALED USE METER HUBS OR EQUIVALENT, SEALING LN'S NOT EFFECTIVE. 2. REMOVE POWERED CIRCUIT GOING THRU THIS BOX. 3. REMOVE GREEN GROUND OR BOND SCREW ON NEUTRAL BUS PNL-P 4. PHONE CABINET BELOW SERVICE IN VIOLATION OF NEC 2002 110-26 CLEARANCE BELOW SERVICE. 5. PERMANENTLY MARK DISCONNECT FOR PNL P MAIN DISCONNECT PNL P, SAME FOR OTHER DISCONNECT. |
|
| 10/24/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NEED THE CITY APPROVED PLANS FOR ELEC. INSPECTION RESCHEDULE 740-6970 |