Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2007 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* 1) PROVIDE PREVIOUSLY REQUESTED DOCUMENTATION FOR EXCESSIVE NAILING AT #5 SHEARWALL IN GARAGE |
|
| 01/10/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/08/2007 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) OVER NAILED SHEARWALLS NAILING OF SHEAR OSB AT 1 TO 1 1/2 INCHES INTO 2 X STUDS NOT ALLOWED MINIMUM 3 X STUDS REQUIRED. HAVE ENGINEER OF RECORD PROVIDE AN APPROVED REPAIR OR ACCEPT RESPONSIBILITY FOR CONDITION OR REPLACE GARAGE #5 SHEARWALL |
|
| 01/04/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BLOCK INTERIOR #2 SHEARWALL 2) NAILS OVER PENETRATING #5 SHEARWALL 3) TECO NAILS ARE NOT PERMITTED FOR APPLIANCES OVER 3/8-1/2" SHEATHING 4) COMPLETE ANCHOR BOLT INSTALLATION 5) ANCHOR BOLTS AT 32" ON CENTER REQUIRED AT #5 SHEARWALL 6) COMPLETE HOLDOWN INSTALLATION 7) DETAIL 5/DT1 REQUIRES HINGE BRACING AT 48" ON CENTER 8) TRUSS # A/C HAS SPLIT VERTICAL MEMBER 9) STOPPED INSPECTION |