Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 01/05/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE CITY OF TUCSON APPROVED ENGINEERING REPAIR DOCUMENTS FOR REPAIR OF POST TENSION FLOOR. REPAIR DOCUMENT MUST BE LISTED BY ADDRESS AND ON FILE WITH CITY OF TUCSON BEFORE FINAL INSPECTION 2) ACCESS TO A/C CONDENSOR DISCONNECT OBSTRUCTED BY CONDENSOR 3) IMPROPER COLOR CODING OF WIRES IN JUNCTION BOX. WHITE WIRES CANNOT BE HOT 4) 4" CLEARANCE REQUIRED BETWEEN SOIL AND WEEP SCREED 5) FAN DISCONNECT NOT READILY ACCESSIBLE 6) SEAL CEILING FURNACE ENCLOSURE 7) GFCI OUTLET REQUIRED WITHIN 24" RT SIDE KITCHEN 8) DISHWASHER DRAIN REQUIRES AIR GAP OR LOOP TO 2" OF SINK FLOOD RIM 9) STOPPED INSPECTION-TO MANY ITEMS |
|
| 01/04/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OBTAIN FINAL FRAMING AND YARD WATER APPROVALS 2) BLACK TAPE REQUIRED ON WHITE CONDUCTOR USED AS HOT 3) DBL LUGGING BREAKERS NOT PERMITTED 4) LABEL SERVICE PANEL WITH STREET ADDRESS 5) NO FUSES IN DISCONNECTS-FIRE UP MECH SYSTEM 6) STOPPED INSPECTION-HOUSE NOT COMPLETE |