Permit: T06CM04770

Parcel: 140420740

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/01/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/20/2006 ELECTRIC - FINAL Partial Approval OK FOR TEMP C/O
NEED APPROVED REVISION ON ELECTRICAL PLAN TO APPROVE FINAL
10/19/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
- COMPLETE SEISMIC INSTALL FOR GRID FIXTURES,
- BOND X-FORMERS TO H20 LINE
- NEED LETTER FROM ARCH. FOR OK TO MOUNT X-FORMER IN CEILING AREA.

RETURN INSP. AFTER HOURS -- PM
RECEIVED CK#56147 FOR $324.00
1. RECEIVED LETTER FROM ARCH. FOR X-FORMER APPROVAL AS INSTALLED ABOVE GRID CEILING.
2. OK SEISMIC WIRES TO FIXTURES.
3. NEED TO SEE PANEL BR - SPLICES WHEN DONE.
4. COMPLETE WATER PIPE BOND TO X-FORMERS

OK TCO