Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/07/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* OK TO TILE 1. SUPPORT VDV AS DISCUSSED |
|
| 11/01/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* FINISH SUPPORTING VDV CABELING -- WE STILL HAVE SOME LAYING ON GRID. |
|
| 10/26/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. VDV CABELING TO BE AS PER 715.3 & 6, 800.3 & 6, 300.11 2. WE HAVE BOX OVERFILL |
|
| 10/23/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* WORK IN PROGRESS MC NOT SUPPORTED LOW VOLTAGE WIRING OVERFILLED J-BOXES K.O BLANKS FIXTURES SUPPORTED/SECURED DON'T USE GRID SUPPORT WIRES FOR EQUIPMENT SUPPORT OPEN J-BOXES |