Permit: T06CM04764

Parcel: 133110130


Addresses:

1350 N KOLB RD #215

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
11/07/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
OK TO TILE
1. SUPPORT VDV AS DISCUSSED
11/01/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
FINISH SUPPORTING VDV CABELING -- WE STILL HAVE SOME LAYING ON GRID.
10/26/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. VDV CABELING TO BE AS PER 715.3 & 6, 800.3 & 6, 300.11
2. WE HAVE BOX OVERFILL
10/23/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
WORK IN PROGRESS
MC NOT SUPPORTED
LOW VOLTAGE WIRING
OVERFILLED J-BOXES
K.O BLANKS
FIXTURES SUPPORTED/SECURED
DON'T USE GRID SUPPORT WIRES FOR EQUIPMENT SUPPORT
OPEN J-BOXES