Permit: T06CM04752

Parcel: 137055110

Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Permit Number - T06CM04752

Inspection Description - ELECTRIC - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
07/22/2008 ELECTRIC - PROGRESS Approved IVRS - Inspection :*
07/17/2008 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
06/23/2008 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
CANCELED
06/20/2008 ELECTRIC - PROGRESS Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
PLEASE ADD MISSING INSPECTION TO PERMIT

1. BELL ENDS TO PROTECT CONDUCTORS NEEDED
251.46 & 300.4
2. CONDUIT TO RISE 3" INTO SES
3. NEED LETTER FOR TORQUE OF EQUIPMENT
4. NEED LETTER FROM ENGINEER FOR GROUNDING ELECTRODE SYSTEM
5. DRIVE GROUND RODS FLUSH
6. ONLY ONE CONDUCTOR PER LUG
06/19/2008 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
02/27/2008 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
OK RESTROOM WALLS, NO FART FANS YET
OK SOFFIT LTG.