Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T06CM04752
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/22/2008 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
07/17/2008 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
06/23/2008 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
06/20/2008 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* PLEASE ADD MISSING INSPECTION TO PERMIT 1. BELL ENDS TO PROTECT CONDUCTORS NEEDED 251.46 & 300.4 2. CONDUIT TO RISE 3" INTO SES 3. NEED LETTER FOR TORQUE OF EQUIPMENT 4. NEED LETTER FROM ENGINEER FOR GROUNDING ELECTRODE SYSTEM 5. DRIVE GROUND RODS FLUSH 6. ONLY ONE CONDUCTOR PER LUG |
|
06/19/2008 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
02/27/2008 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* OK RESTROOM WALLS, NO FART FANS YET OK SOFFIT LTG. |