Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/28/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MAIN DISCONNECT TO BE PERMANENTLY MARKED - NO MARKER. 2. NEW 200A DISCONNECT REQUIRES A MAIN BONDING SCREW AT NEUTRAL TERMINATION, BOND GROUND WIRE TO ENCLOSURE. 3. CLASS R FUSES REQUIRE REJECT PINS. 4. AT GUTTER DO NOT USE NEUTRAL TO BOND BUSHING BOND BUSHING TO ENCLOSURE. 5. REMOVE GREEN BOND SCREW AT SUB-PANEL IT TIES NEUTRAL TO ENCLOSURE. 6. REMOVE 20A SQD BREAKER IN SUB-PANEL & USE SIEMENS APPROVED TYPE. 7. EM LIGHT AT NORTH SIDE - BEHIND DUCT WORK - LOWER 8. UNAPPROVED FITTING INSIDE AT DISCONNECT AT NORTH - CUT CONNECTOR 9. FIX COVER ON NORTH GFI -- BROKEN |
|
| 11/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* UNDERGROUND INSPECTED 11/9/06 BY BOB S. |