Permit: T06CM04738

Parcel: 10601216A


Addresses:

519 E PRINCE RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/30/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/28/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MAIN DISCONNECT TO BE PERMANENTLY MARKED - NO MARKER.
2. NEW 200A DISCONNECT REQUIRES A MAIN BONDING SCREW AT NEUTRAL TERMINATION, BOND GROUND WIRE TO ENCLOSURE.
3. CLASS R FUSES REQUIRE REJECT PINS.
4. AT GUTTER DO NOT USE NEUTRAL TO BOND BUSHING
BOND BUSHING TO ENCLOSURE.
5. REMOVE GREEN BOND SCREW AT SUB-PANEL
IT TIES NEUTRAL TO ENCLOSURE.
6. REMOVE 20A SQD BREAKER IN SUB-PANEL & USE SIEMENS APPROVED TYPE.
7. EM LIGHT AT NORTH SIDE - BEHIND DUCT WORK - LOWER
8. UNAPPROVED FITTING INSIDE AT DISCONNECT AT NORTH - CUT CONNECTOR
9. FIX COVER ON NORTH GFI -- BROKEN
11/13/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
UNDERGROUND INSPECTED 11/9/06 BY BOB S.