Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
Permit Number - T06CM04690
Inspection Description - REINFORCED MASONRY PRE-GROUT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/07/2008 | REINFORCED MASONRY PRE-GROUT | Approved | IVRS - Inspection :* | |
11/03/2008 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO REVISE PLANS TO SHOW SPECS FOR RASTRA-NOT MICKEY BLOCK 2) HORIZONTAL REBAR IS AT 30" ON CENTER, DRAWING SHOWS 18" ON CENTER |