Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06CM04683
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/19/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* THIS BUILDING HAS NON-METALLIC INTERIOR WATER PIPING. 1. DOOR LOCKED -- NO ACCESS REINSPECTED 2:15 PM PLUMBING FINAL OK OK FOR C OF O S.T.O.I |
|
09/15/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO AVB ON HOSE BIBB 2. NO FULL PORT VALVE AT WATER HEATER 3. CONTINUED "NOT READY'S" MAY RESULT IN A REINSPECTION FEE. 4. AT KITCHEN SINK -- MAY NOT INTERMINGLE MATERIAL TYPES I.E ABS AND PVC MUST USE DRAINAGE FITTINGS - PVC PRESSURE 45 DEG. NOT APPROVED FOR DRAINAGE. |
|
09/08/2006 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* - OK TO COVER WALLS - FOR FINAL INSPECTION, WH SUPPLY VALVE SHALL BE FULL-PORT, - SEDIMENT TRAPS REQUIRED ON GAS PIPING - ALL FIXTURES SHALL BE INSTALLED FOR FINAL INSPECTION - ALSO, PLEASE PROVIDE A HOSE BIB VACUUM BREAKER ON EXTERIOR HB ASSOCIATED W/THIS UNIT. |