Permit: T06CM04683

Parcel: 11202033P


Addresses:

2000 E ROGER RD G

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
09/19/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
09/06/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
CAST TO PLASTIC TRANSITION IS LOOSE
RECONNECT USING MISSION COUPLINGS
ALSO PVC AT CEILING IS BURNED - REPLACE ANY DAMAGED PIPING.
PLEASE TEMP CAP ANY OPEN SEWER PIPES DURING CONSTRUCTION.
CONDENSATE, T&P DRAIN, AND DRAIN PAN ARE OK
08/31/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
- PRESSURE TEST HOLDING
- UPC REQUIRES THAT A WH INSTALLED ON A SUB-FLOOR HAVE A DRAIN PAN WITH A DRAIN TO EXTERIOR.
- PROTECT DRAIN T&P WITH SAFETY PLATES.
- PROTECT CONDENSATE TRAP SEAL W/TRAP PRIMER OR CAP AND RUN A NEW CONDENSATE DRAIN TO APPROVED LOCATION.
08/23/2006 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
PROVIDE PRESSURE TEST
SUPPORT PIPING
SUPPORT T&P PIPING
CONDENSATE DWV APPEARS TO BE BURNT AT CEILING