Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM04683
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
09/27/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. KITCHEN LIGHT NOT WORKING AND END CAPS NOT INSTALLED. 2. HOOD FANS NEED CORRECT SIZE BULB & PROPER ROMEX CONNECTOR. 3. INSTALL ANTI-TIP DEVICE ON RANGE (SEE INSTRUCTIONS) 4. INSTALL CORRECT SIZE BULBS IN ALL LIGHT FIXTURES. 5. SMOKE DETECTORS TO BE INTER-CONNECTED. 6. CEILING FAN NOT WORKING 7. PANEL DIRECTORY UPSIDE DOWN AND NOT MARKED CORRECTLY. 8. FURNACE CORD NEEDS CONNECTOR 9. MUST PAY REINSPECTION FEE PRIOR TO FINAL APPROVAL. |
|
09/19/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) POWER HAS BEEN APPROVED 2) CALL FOR FINAL AFTER POWER IS ON AND ELECTRICIANS HAVE CHECKED THEIR WORK |
|
09/18/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |