Permit: T06CM04683

Parcel: 11202033P


Addresses:

2000 E ROGER RD G

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/06/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/27/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. KITCHEN LIGHT NOT WORKING AND END CAPS NOT INSTALLED.
2. HOOD FANS NEED CORRECT SIZE BULB & PROPER ROMEX CONNECTOR.
3. INSTALL ANTI-TIP DEVICE ON RANGE (SEE INSTRUCTIONS)
4. INSTALL CORRECT SIZE BULBS IN ALL LIGHT FIXTURES.
5. SMOKE DETECTORS TO BE INTER-CONNECTED.
6. CEILING FAN NOT WORKING
7. PANEL DIRECTORY UPSIDE DOWN AND NOT MARKED CORRECTLY.
8. FURNACE CORD NEEDS CONNECTOR
9. MUST PAY REINSPECTION FEE PRIOR TO FINAL APPROVAL.
09/19/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) POWER HAS BEEN APPROVED
2) CALL FOR FINAL AFTER POWER IS ON AND ELECTRICIANS HAVE CHECKED THEIR WORK
09/18/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*