Permit: T06CM04683

Parcel: 11202033P


Addresses:

2000 E ROGER RD G


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM04683

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/06/2006 ELECTRIC - INTERMEDIATE Approved
09/06/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SMOKE DETECTORS NEED TO BE INTER-CONNECTED
2. NEED BUSHING #4 AND LARGER CONDUCTOR
3. GROUND EXTERIOR LIGHT BOX

OK COVER AFTER CORRECTIONS MADE
09/01/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. CABLES TO BE SECURED TO BOXES 312.5
2. SECURE NM CABLE WITHIN 12" OF BOX & PANEL NOT KO BUSHINGS.
3. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS.
4. USE CORRECT SIZED LUG PER LISTING
5. TIGHTEN LOOSE CONNECTORS
6. FIRE PROOFING TO BE ENTIRE BOX (BX PUTTY PADS)
08/25/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. HAVE OVERFILLED J-BOXES - NEC 314.16
2. LAY OUT RECEPTACLES PER CODE - NEC 210.50
3. TIGHTEN ALL WIRE NUTS - NEC 110.14
ALSO, SOME NUTS MISSING.
4. NEED MINIMUM (2) 20 AMP. COUNTERTOP CKTS IN KITCHEN WIRE PER NEC 210.52 WITH NO OTHER LOADS.
5. BATH GFI TO BE WIRED PER NEC 210.11(C)(3) AND INSTALL EX. FAN.
6. PROPERLY GROUND ALL METAL BOXES -- NEC 250
7. NEED SMOKE DETECTOR IN BEDROOM AND HALLWAY
8. NEED BUSHING FOR 34 AND LARGER CONDUCTOR -
NEC 300.4
9. ARC FAULT PROTECTION REQUIRED FOR ALL BEDROOM BRANCH CKTS PER NEC 210.12
10. EQUIPMENT GROUND TO PANEL BOARD UNDERSIZED -
NEC 250.122
11. IDENTIFY UNIT @ SERVICE - NEC 230
12. SECURE ROMEX INTO BOX PER NEC 334.30
13. PROVIDE DEDICATED CKT TO FURNACE - NEC 220
14. FRONT EXTERIOR LIGHT NEEDS PROPER ROMEX ENTRY

SABINO 977-8313