Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM04683
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2006 | ELECTRIC - INTERMEDIATE | Approved | ||
09/06/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SMOKE DETECTORS NEED TO BE INTER-CONNECTED 2. NEED BUSHING #4 AND LARGER CONDUCTOR 3. GROUND EXTERIOR LIGHT BOX OK COVER AFTER CORRECTIONS MADE |
|
09/01/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. CABLES TO BE SECURED TO BOXES 312.5 2. SECURE NM CABLE WITHIN 12" OF BOX & PANEL NOT KO BUSHINGS. 3. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS. 4. USE CORRECT SIZED LUG PER LISTING 5. TIGHTEN LOOSE CONNECTORS 6. FIRE PROOFING TO BE ENTIRE BOX (BX PUTTY PADS) |
|
08/25/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. HAVE OVERFILLED J-BOXES - NEC 314.16 2. LAY OUT RECEPTACLES PER CODE - NEC 210.50 3. TIGHTEN ALL WIRE NUTS - NEC 110.14 ALSO, SOME NUTS MISSING. 4. NEED MINIMUM (2) 20 AMP. COUNTERTOP CKTS IN KITCHEN WIRE PER NEC 210.52 WITH NO OTHER LOADS. 5. BATH GFI TO BE WIRED PER NEC 210.11(C)(3) AND INSTALL EX. FAN. 6. PROPERLY GROUND ALL METAL BOXES -- NEC 250 7. NEED SMOKE DETECTOR IN BEDROOM AND HALLWAY 8. NEED BUSHING FOR 34 AND LARGER CONDUCTOR - NEC 300.4 9. ARC FAULT PROTECTION REQUIRED FOR ALL BEDROOM BRANCH CKTS PER NEC 210.12 10. EQUIPMENT GROUND TO PANEL BOARD UNDERSIZED - NEC 250.122 11. IDENTIFY UNIT @ SERVICE - NEC 230 12. SECURE ROMEX INTO BOX PER NEC 334.30 13. PROVIDE DEDICATED CKT TO FURNACE - NEC 220 14. FRONT EXTERIOR LIGHT NEEDS PROPER ROMEX ENTRY SABINO 977-8313 |