Permit: T06CM04678

Parcel: 140420740

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/22/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/21/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEISMIC WIRES TO BE WRAPPED AROUND FIXTURE HOUSING, NOT MC CABLE FOR SEISMIC SUPPORT, WRAP WIRES AT LEAST 3 WRAPS NOT JUST LOOPED.
2. SUPPORT LONG RUNS OF MC CABLE PER NEC WITHIN 12" AT TERMINATIONS AND AT 6' INTERVALS. 6' OR LESS FIXTURE TAILS ARE EXEMPT. COVER ALL J-BOXES

OK TCO FOR STOCKING

RETURN AFTER HRS. - DENIED, NO COMPLIANCE WITH NOTE PREVIOUS INSP.