Permit: T06CM04662

Parcel: 127022830


Addresses:

1020 N WOODLAND AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/19/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
AIR BALANCE OK
10/11/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
FRESH AIR INTAKE GOES ON THE RETURN SECTION OF
AC UNIT - NOT THE SUPPLY SECTION. HOW COULD THIS POSSIBLY BE AIR BALANCED? PROVIDE AIR BALANCE FROM INDEPENDENT CONTRACTOR.
10/10/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
09/25/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
FLEX CONNECTOR NOT LISTED FOR TYPE 1
CLEANOUT DOORS OK
FINISH CONDENSATE DRAIN
FINISH INTERLOCK
PROVIDE AIR BALANCE
09/18/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- THE STOVE ON WHEELS REQUIRES A QUICK DISCONNECT HOSE AND RESTRAINT CABLE.
- PROVIDE A FRESH AIR INTAKE
- SCRATCH OFF THE UNIT DATA PLATE W/PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY
- PROVIDE A CONDENSATE DRAIN TO AN APPROVED LOCATION
- DO NOT USE ESSES & DRIVES TO SUPPORT DUCT ON ROOF
- PROVIDE THE LISTING FOR THE FLEX CONNECTOR USED FOR TYPE 1 FAN
- INTERLOCK MAKE UP AIR FAN WITH EXHAUST HOOD
- PROVIDE AIR BALANCE REPORT