Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* AIR BALANCE OK |
|
| 10/11/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* FRESH AIR INTAKE GOES ON THE RETURN SECTION OF AC UNIT - NOT THE SUPPLY SECTION. HOW COULD THIS POSSIBLY BE AIR BALANCED? PROVIDE AIR BALANCE FROM INDEPENDENT CONTRACTOR. |
|
| 10/10/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 09/25/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* FLEX CONNECTOR NOT LISTED FOR TYPE 1 CLEANOUT DOORS OK FINISH CONDENSATE DRAIN FINISH INTERLOCK PROVIDE AIR BALANCE |
|
| 09/18/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - THE STOVE ON WHEELS REQUIRES A QUICK DISCONNECT HOSE AND RESTRAINT CABLE. - PROVIDE A FRESH AIR INTAKE - SCRATCH OFF THE UNIT DATA PLATE W/PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY - PROVIDE A CONDENSATE DRAIN TO AN APPROVED LOCATION - DO NOT USE ESSES & DRIVES TO SUPPORT DUCT ON ROOF - PROVIDE THE LISTING FOR THE FLEX CONNECTOR USED FOR TYPE 1 FAN - INTERLOCK MAKE UP AIR FAN WITH EXHAUST HOOD - PROVIDE AIR BALANCE REPORT |