Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* HBS ON EXTERIOR |
|
| 10/04/2007 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE BACKFLOW CERTS ON NEW ASSEMBLIES PROVIDE PLANS GAS TEST ON RE-WORK OK |
|
| 09/25/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* - HIGH HAZARD BACKFLOW PROTECTION NEEDED AT WHIRLPOOL - COMPLETE WORK. GLUE AND SUPPORT DRAINS - PROVIDE APPROVED PLAN REVISIONS FOR ALL FIXTURES AND CHANGES - CAP ALL UNUSED OUTLETS. GAS, WATER, SEWER |
|
| 09/18/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SLOPE AND CLEANOUTS REQUIRED ON IDW - PROPER USE OF DRAINAGE FITTINGS REQUIRED ON IDW - PROVIDE ACCESS TO CLEANOUTS - SEAL ALL CLEANOUTS - TRIM OUT CLEANOUT AT DW SINK - WHIRLPOOL SPA REQUIRES RP BACKFLOW PREVENTORS ON HOT AND COLD - PUBLIC USE TOILETS REQUIRE OPEN FRONT SEATS - FS'S REQUIRE STRAINERS & GRATES - PLUG UNUSED EXISTING DRAINS - PROVIDE A CLEAN BACTERIA REPORT AS REQUIRED IN UPC SEC 609.3 -- RESTRAINTS ON GAS EQUIPT. |