Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/24/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | STEVE 909-5638 CONTRACTOR CANCELLED |
|
| 08/17/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* - REDLINE CHANGES - SUPPORT PIPING IN MECHANICAL ROOMS AND AT METER - PIPE SUPPORTS ON ROOF ARE CUTTING INTO ROOF - INSTALL PIPE SUPPORTS THAT WON'T DAMAGE ROOF (WEATHER RESISTANT) |
|
| 07/12/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* VENT FOR FLOW CONTROL OK WASHER BOXES WATER & DWV OK SUBJECT TO APPROVED PLAN REVISION FOR USE AAV AND ADDITION OF 3RD WB HAMMER ARRESTORS INSTALLED IN WALL |
|
| 07/05/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ROUGH SOIL PIPING AT TUB OK ROUGH SOIL PIPING AND VENT AT FS, KITCHEN OK |