Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/04/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) LOWER DECK 1"-2" FOR ACCESS TO BOTTOM OF DISCONNECTS. ALSO DOOR TO OPEN 2) WHAT IS NEW WIRING TO OUTSIDE OF BLDG ? DO YOU HAVE CLASS 1 AND CLASS 2 WIRING IN SAME RACEWAY 3) WITH PANELS OPEN PLEASE CLEAN EXCESS DIRT AND DEBRIS 4) FINISH PANEL SCHEDULES |
|
| 09/25/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. TIGHTEN LOOSE FITTINGS A/C WEST & EAST 2. MAINTAIN WORKING CLEARANCES A/C EAST 3. FINISH #2 & #15 PREVIOUS INSPECTION |
|
| 09/18/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOX UNDER DISHWASHER EXPOSED TO EXCESS WATER TO BE FOR WET LOCATION 2. SEPARATE NEUTRALS AND GROUNDS AT SUB-PANELS 3. CORRECTLY IDENTIFY NEUTRAL CONDUCTORS 200.6 4. NEED REVISED PANEL SCHEDULES PER 408.4 5. PROPERLY CAP UNUSED CONDUCTORS - NOT TAPE 6. FILL UNUSED OPENING 7. SUPPORT EXIT LIGHT IN GRID & MC CABLE 8. ATTACH 2X4 TO GRID OFFICE 9. GROUND FOR HYDRO MASSAGE TUB TO BE SOLID AS PER 480 10. CORDS & BOXES NOT ALLOWED FOR PERMANENT WIRING METHOD 11. MISSING LIGHT IN BATHROOM WALL 12. PROPERLY GROUND RECEPTACLES - 3/4 OF A TURN IN A CLOCKWISE DIRECTION 13. MAKE UP FOR BATH LIGHT TO BE IN BOX - ALSO, USE CORRECT METHOD FOR GROUNDING 14. NO MORE THAN 360 DEG. IN A CONDUIT RUN 15. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 |