Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T06CM04662

Parcel: 127022830


Addresses:

1020 N WOODLAND AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/09/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/04/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) LOWER DECK 1"-2" FOR ACCESS TO BOTTOM OF DISCONNECTS. ALSO DOOR TO OPEN
2) WHAT IS NEW WIRING TO OUTSIDE OF BLDG ? DO YOU HAVE CLASS 1 AND CLASS 2 WIRING IN SAME RACEWAY
3) WITH PANELS OPEN PLEASE CLEAN EXCESS DIRT AND DEBRIS
4) FINISH PANEL SCHEDULES
09/25/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. TIGHTEN LOOSE FITTINGS A/C WEST & EAST
2. MAINTAIN WORKING CLEARANCES A/C EAST
3. FINISH #2 & #15 PREVIOUS INSPECTION
09/18/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOX UNDER DISHWASHER EXPOSED TO EXCESS WATER TO BE FOR WET LOCATION
2. SEPARATE NEUTRALS AND GROUNDS AT SUB-PANELS
3. CORRECTLY IDENTIFY NEUTRAL CONDUCTORS 200.6
4. NEED REVISED PANEL SCHEDULES PER 408.4
5. PROPERLY CAP UNUSED CONDUCTORS - NOT TAPE
6. FILL UNUSED OPENING
7. SUPPORT EXIT LIGHT IN GRID & MC CABLE
8. ATTACH 2X4 TO GRID OFFICE
9. GROUND FOR HYDRO MASSAGE TUB TO BE SOLID
AS PER 480
10. CORDS & BOXES NOT ALLOWED FOR PERMANENT WIRING METHOD
11. MISSING LIGHT IN BATHROOM WALL
12. PROPERLY GROUND RECEPTACLES - 3/4 OF A TURN IN A CLOCKWISE DIRECTION
13. MAKE UP FOR BATH LIGHT TO BE IN BOX - ALSO, USE CORRECT METHOD FOR GROUNDING
14. NO MORE THAN 360 DEG. IN A CONDUIT RUN
15. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20