Permit: T06CM04662

Parcel: 127022830


Addresses:

1020 N WOODLAND AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/09/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/20/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL AT JACUZZI
07/18/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
EXTEND BOX OUT TO SURFACE
07/12/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROTECT NM-B CABLE IN PLASTER
2. NOTE: INSTALL JACUZZI PER 680

OK BATHROOMS & LAUNDRY
SUBJECT TO APPROVED PLANS
06/18/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. JUNCTION BOXES TO BE ACCESSIBLE
2. CLEAN, FOREIGN MATERIAL FROM CONDUCTIVE
SURFACES 110.12
3. SEAL UNUSED OPENINGS IN PANEL "KITCHEN" ALSO SECURE CABLES -- 312.5
4. PLEASE HAVE ARCHITECT AUTHORIZE USAGE OF "NM" CABLE
5. ATTACH FIXTURES TO GRID - 410.16
6. SUPPORT VDV CABLING - 725.6
7. PLEASE INSTALL WORK AS PER PLANS OR REVISE PLANS WHERE IS ARTICLE 415
06/14/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) CONTRACTOR TO SCHEDULE WITH ELECTRICIAN TO MEET ON JOB