Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/12/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/05/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. KITCHEN COUNTERTOP RECEPTACLES TO BE GFCI PROTECTED - 210.8 2. ALL OUTLETS IN DWELLING UNITS TO BE ARC FAULT PROTECTED - 210.12 3. USE LISTED AND APPROVED APPLIANCE PIGTAILS 4. ANTI-TIP DEVICE FOR RANGE NEEDED 5. CLEAN EXCESS FOREIGN MATERIAL FROM PANEL -- 110.12 6. TIGHTEN LOOSE FITTINGS A/C 7. EXPOSED CONDUCTORS PASSING THROUGH WALL 8. CANNOT TRIM CONDUCTORS -- USE APPROVED LUG AND ALL STRANDS 9. INSTALL ALL STRANDS UNDER LUGS |
|
| 08/31/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/27/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |