Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/01/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 05/24/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. SUPPORT NM WITHIN 12" OF BOXES & 6' -- 334.20 ALSO, SE CABLE 2. SUPPORT VDV CABLING PER 725.6 & 800.6 3. FILL UNUSED OPENINGS IN BOXES 4. TIGHTEN LOOSE FITTINGS 5. RECEPTACLE COVER OUTDOORS TO BE AS PER 406.8 6. SECURE CABLE TO METAL BOXES & GROUND 7. PLEASE VERIFY GROUND RODS & UNLOCK SERVICE 8. PAN BOX OVERFILLED |