Permit: T06CM04661

Parcel: 127022830


Addresses:

5419 E 2ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/02/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/01/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/24/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. SUPPORT NM WITHIN 12" OF BOXES & 6' -- 334.20
ALSO, SE CABLE
2. SUPPORT VDV CABLING PER 725.6 & 800.6
3. FILL UNUSED OPENINGS IN BOXES
4. TIGHTEN LOOSE FITTINGS
5. RECEPTACLE COVER OUTDOORS TO BE AS PER 406.8
6. SECURE CABLE TO METAL BOXES & GROUND
7. PLEASE VERIFY GROUND RODS & UNLOCK SERVICE
8. PAN BOX OVERFILLED