Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2006 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 12/06/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS 4 AND 5 OF 11/30/06 INSPECTION NOT COMPLIED WITH |
|
| 11/30/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ACCESS TO A/C CONDENSOR DISCONNECT OBSTRUCTED BY UNIT. MUST HAVE 30" X 30" WORK AREA 2) A/C CONDENSOR NOT LEVEL 3) MAX ALLOWED FUSE/LB FOR CONDENSOR 30A-50A INSTALLED 4) STUCCO WEEP SCREED MUST BE 4" ABOVE SOIL 5) STUCCO WEEP SCREED CANNOT BE COVERED BY CONCRETE MUST HAVE 2" CLEARANCE TO CONCRETE 6) OPEN GROUND BATHROOM GFCI 7) INCANDESCENT LIGHT MUST BE 12" HORIZONTALLY FROM CLOSET SHELF |