Permit: T06CM04624

Parcel: 11451216G

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/20/2006 ELECTRIC - INTERMEDIATE Approved
09/05/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. USE APPROVED FITTINGS FOR M/C CABLES
2. GROUND JUNCTION BOXES
3. SUPPORT CHASE RACEWAY
4. VERIFY BOX FILL PER 416
5. SUPPORT M/C CABLES WITHIN 12" OF BOXES
6. VDV CABLEING TO BE AS PER 725.3 & 6, 800.3 & 6
7. PLEASE REVISE PLANS TO REFLECT WORK DONE. PLANS WILL NEED NEW CITY STAMPS
8. RELOCATED LIGHTS TO BE ATTACHED TO GRID AND HAVE
2 SUPPORT WIRES PER FIXTURE. 1 PER EXIT SIGN. 1 PER 4'
OF TRAC LIGHTING.
9. AREAS ARE BEING OCCUPIED DURING CONSTRUCTION.