Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM04624
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/20/2006 | ELECTRIC - INTERMEDIATE | Approved | ||
09/05/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. USE APPROVED FITTINGS FOR M/C CABLES 2. GROUND JUNCTION BOXES 3. SUPPORT CHASE RACEWAY 4. VERIFY BOX FILL PER 416 5. SUPPORT M/C CABLES WITHIN 12" OF BOXES 6. VDV CABLEING TO BE AS PER 725.3 & 6, 800.3 & 6 7. PLEASE REVISE PLANS TO REFLECT WORK DONE. PLANS WILL NEED NEW CITY STAMPS 8. RELOCATED LIGHTS TO BE ATTACHED TO GRID AND HAVE 2 SUPPORT WIRES PER FIXTURE. 1 PER EXIT SIGN. 1 PER 4' OF TRAC LIGHTING. 9. AREAS ARE BEING OCCUPIED DURING CONSTRUCTION. |