Permit: T06CM04622

Parcel: 106121250

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/30/2007 ELECTRIC - FINAL Approved
07/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SECURE RANGE ANTI-TIP DEVICE TO FLOOR
2. HAVE SEVERAL LOOSE RECEPTACLES, THEY ALSO NEED TO BE SQUARE WITH COVER AND COVER FLUSH TO WALL
3. PANEL DIRECTORY TO BE CORRECT AND LEGIBLE