Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/30/2007 | ELECTRIC - FINAL | Approved | ||
| 07/24/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SECURE RANGE ANTI-TIP DEVICE TO FLOOR 2. HAVE SEVERAL LOOSE RECEPTACLES, THEY ALSO NEED TO BE SQUARE WITH COVER AND COVER FLUSH TO WALL 3. PANEL DIRECTORY TO BE CORRECT AND LEGIBLE 4. ROOFTOP UNIT IS IDENTIFIED ON DATA LABEL AS A DUAL SUPPLY BUT YOU HAVE SINGLE SUPPLY? IF SINGLE SUPPLY (REIDENTIFY) MINIMUM CKT AMPACITY WITH 9.6 KW HEAT STRIPS IS 96 AMPS DISCONNECTING MEANS NEED TO BE RATED 115% OF UNIT FLA -- SEE NEC 440.12 B2 |