Permit: T06CM04622

Parcel: 106121250

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/10/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/09/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/26/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUND ALL METAL BOXES
2) NAIL PLATE WIRES PER NEC 300.4
3) PROTECT WIRES PARALLEL TO FRAMING MEMBERS PER NEC 300.4
4) INSTALL BUSHING ON PVC FEEDER TO PANEL PER NEC 352.46
5) SECURE SUPPORT ROMEX PER NEC 334.30 & 314.17
6) ROMEX SHEATH TO EXTEND 1/4" INTO BOX PER NEC 314.17
7) KITCHEN RECEPTACLE TO BE INSTALLED PER NEC 210.52
8) CHECK LOCATION OF WATER HTR CKT LOOKS TO BE NOT ACCESSIBLE AND WILL BE BEHIND WATER HEATER
9) ROUTE CABLE FOR ROOF TOP UNIT
10) RECALL WHEN READY