Permit: T06CM04617

Parcel: 11709190A


Addresses:

1155 S 7TH AV

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
05/15/2007 BUILDING - FINAL Approved IVRS - Inspection :*
05/10/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED INSULATION CERTS
05/08/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OUTSIDE GFI RECEPTACLES NOT WORKING BECAUSE OF PAINT
2) NO GAS BOND AT PANEL
3) NEED LANDING AT BACK DOOR
4) A/C OVERFLOW NEEDS TO TERMINATE 6" OF GROUND
5) CAULK THE BASE OF TOILETS (2)
6) NEED 15 PSI TO CHECK GAS FOR FINAL TEST
7) LIGHTING IN CLOSET DOES NOT MEET CODE
8) W/H VENT HAS 90 ELBOW S. ON DBL VENT
9) RANGE HOOD WIRED WRONG
05/07/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ACCESS 8:10 AM
05/04/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) POST ADDRESS NUMBERS ON HOUSE
2) COMPLETE LATH GRADING
3) INSTALL DRIP LEG
4) GAS APPLIANCES
5) PAINT EXPOSED VENTS ON ROOF
6) NEED LADDER TO ACCESS ROOF
7) INSTALL ANTI-SIPHON HOSE BIBS
8) DRYER REQUIRES 4 WIRE SYSTEM
9) CAULK BASE OF TOILETS
10) CANNOT HAVE EXPOSED CLOSET BULBS
11) NEED INSULATION CERT
12) PLEASE CALL IN ALL FINALS
13) STOPPED INSPECTION