Permit: T06CM04613

Parcel: 137055090

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T06CM04613

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/15/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
04/04/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
DUCT SMOKE TEST OK
SEE BUILDING INSPECTOR FOR TEMP C OF O
04/03/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
UNITS MUST BE OPERATIONAL TO TEST DUCT
SMOKE DETECTORS PRIOR TO TEMP C OF O
04/01/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- L.P OFFICE CONDENSATE PIPING BACKWARDS, MUST HAVE TRAPS ON CONDENSATE PIPING, COMPLETE INSULATION ON REF. PIPING
- VERIFY DUCT SMOKE DETECTORS AT SUPPLY ON UNITS (RTU)

D.S.D TEST NOT COMPLETE