Permit: T06CM04613

Parcel: 137055090

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/15/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/14/2008 ELECTRIC - FINAL Cancelled IVRS - RI canceled
04/25/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
CHECK FOR EXIT SIGN

REFLECTORS (SHROUDS) MISSING ON AUTO SHOP FIXTURES
04/23/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- SEE NOTE #3
3 IN SALES FLOOR
2 IN STOCK ROOM
- REFLECTORS STILL MISSING IN AUTO SHOP
- TEST OUTDOOR LIGHTING, CALL FOR INSPECTION
04/23/2008 ELECTRIC - FINAL Partial Approval CONTR. REQUEST AFTER HRS. REINSP. FOR TCO
PAID $150.00 AT PERMIT COUNTER

OK TCO TO OPEN
- CHECK MISSING KO'S NORTH END OF SALES FLOOR
- 2X4 AT ENTRY SHOULD BE ON UNSWITCHED CIRCUITS
04/22/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
RECALL FINAL WHEN ALL COMPLETE
04/10/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
- OPEN JBOX IN SMALL OFFICE BY ENTRY AT FRONT OF STORE
EXPOSED SPLICES, USE BOX EXTENSION
- COMPLETE EM LTG WIRING
- CLOSE UNUSED OPENINGS IN J-BOXES THROUGHOUT STORE CEILING
- NEED TO TEST EM LTG
- REFLECTORS MISSING IN AUTO SHOP
04/03/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TCO FOR STOCKING
SEE NOTES LAST INSP.
04/01/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GRID FIXTURES NEED 2 SEISMIC WIRES EACH, 2 SCREWS TO FASTEN TO GRID
2. FA OR OTHER DEVICES NEED ADDITIONAL SUPPORT OTHER THAN CEILING TILE - SEISMIC TO STRUCTURE
3. CLOSE UNUSED OPENINGS IN BOXES
4. CALL FOR ABOVE CEILING INSP. CLOSE UP J-BOXES, CK FOR OVERFILL ADD EXTENSIONS WHERE NECESSARY
5. COMPLETE EM. LTG. & POWER CHECK
6. COMPLETE GONDOLA WIRING
7. INSTALL INSULATING BUSHINGS IN ELECTRICAL EQUIP. WHERE REQUIRED PER CODE EQUIP. GROUNDS TO BE SIZED PER 250 NEC -- ELECTRIC ROOM #104
8. SECURITY & FA NOT COMPLETE
9. OK ROOF ELECTRIC
10. TIE UP FLEX OFF GRID
11. DON'T CALL FOR FINAL INSPECTION UNTIL READY FOR ALL OR A SPECIFIC AREA