Permit: T06CM04613

Parcel: 137055090

Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Permit Number - T06CM04613

Inspection Description - ELECTRIC - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
04/25/2008 ELECTRIC - PROGRESS Approved IVRS - Inspection :*
03/24/2008 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
OK ELECTRICAL PANELS & X-FORMER MAKE UP, GROUNDING
03/18/2008 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
03/10/2008 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) CALLED INTO OFFICE PER PM CLEARANCE
03/07/2008 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
- INSTALL BOND BUSHING ON 150KVA XFORMER FLEX CONNECTION, GUTTER INSTALLATION NOT APPROVED
- COMPLETE TERMINATION AND REMOVE COVERS OF DIST. EQUIP. FOR INSP.
03/06/2008 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
- OK WATER PIPE, BLD. STEEL BONDING
- RECEIVED LETTER OF TORQUE
03/04/2008 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
- OK UFER & GEAR GROUNDING
- PROVIDE LETTER OF TORQUE FOR SES
- POST BOND FOR TEMP POWER FOR TEST
02/15/2008 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
OK STUD WALLS, OFFICE, RESTROOM IN BACK OF STORE