Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/06/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/05/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. RELOCATED LIGHTING TO HAVE 2 SUPPORT WIRES. 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE IN NON-COMBUSTIBLES TO USE APPROVED EXTENDER RINGS 314.20 3. DEVICES WITH EXCESS PAINT TO BE CLEANED OR REPLACED 110.12 4. EXISTING TO BE AS PER 517.13 (LAST INSPECTION). |