Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 03/29/2007 | FRAMING | Partial Approval | IVRS - Inspection :* 1) REAR ADDITION 2) COMBO AND RELIEF REQUIRED AT WATER HEATER TO BE PROVIDED PRIOR TO FINAL 3) OK TO INSULATE AND DRYWALL REAR ADDITION |
|
| 03/19/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE FRAMING HALLWAY 2) 2 POINT BEARING TRUSSES ALLOW 1/2" FOR DEFLECTION 3) AB'S ALL PLATE JOINTS 3"-12"/ATTIC ACCESS MISSING 4) OUTLETS KITCHEN 5) EXPOSE COPPER BOND LAUNDRY 6) MISSING LAUNDRY OUTLET/RAISE TO 42" 7) 12" CLEARANCE PEX FROM CANS AND TERMINATE HOMERUNS IN BOX 8) HIGH/LOW COMBSUTION NEEDED GAS WATER HEATER 9) MISSING 6 X 6 CFM MASTER CLOSET 10) PROVIDE GAS BOND 11) FASTEN LATHE 6" ON CENTER ALL TOP AND BOTTOM PLATES 12) BLOCK REGISTER BOOTS 3 SIDES AT EXISTING TO LAUNDRY 13) HARD WIRE SMOKE DETECTORS EXISTING BEDROOMS AND HALLWAY 14) STOPPED INSPECTION |
|
| 03/08/2007 | FRAMING | Partial Approval | IVRS - Inspection :* 1) PARTIAL UNTIL ALL INTERMEDIATES HAVE BEEN APPROVED |