Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. #6 SMALLER GROUND TO BE GREEN ENTIRE LENGTH NEC 250.119 2. MULTI-WIRE BRANCH CKT'S WITH SHARED NEUTRALS NEED TO HAVE PHASE CONDUCTORS TERMINATE ON SEPARATE PHASES -- NEC 100 3. PROPERLY IDENTIFY FEEDER BREAKER -- NEC 408.4 4. ON ROOF: A. DATA PLATE FOR AC NOT READABLE ---- RE-IDENTIFY B. STRAP FLEX WITHIN 12" OF TERMINATIONS C. SECURE SERVICE RECEPTACLE BETTER D. IDENTIFY AC DISCONNECTS & INSTALL MISSING SIDE SCREW FOR COVER. |