Permit: T06CM04586

Parcel: 11520007B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM04586

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/10/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. #6 SMALLER GROUND TO BE GREEN ENTIRE LENGTH
NEC 250.119
2. MULTI-WIRE BRANCH CKT'S WITH SHARED NEUTRALS NEED TO HAVE PHASE CONDUCTORS TERMINATE ON SEPARATE PHASES -- NEC 100
3. PROPERLY IDENTIFY FEEDER BREAKER -- NEC 408.4
4. ON ROOF:
A. DATA PLATE FOR AC NOT READABLE ---- RE-IDENTIFY
B. STRAP FLEX WITHIN 12" OF TERMINATIONS
C. SECURE SERVICE RECEPTACLE BETTER
D. IDENTIFY AC DISCONNECTS & INSTALL MISSING SIDE SCREW FOR COVER.