Permit: T06CM04584

Parcel: 12416093A

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
08/14/2007 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
OK FOR SHEETROCK
YOU WERE TOLD TO REMOVE ALL TAPE ON EXPOSED DUCT PRIOR TO SEALING JOINTS. NEED TO SEE DUCT LINER IN EXPOSED DUCT ON ROOF. FAILURE TO COMPLY WITH THESE ITEMS WILL RESULT IN A REINSPECTION FEE ON FINAL
08/10/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PRIMER IS REQUIRED PRIOR TO GLUING PVC FITTINGS
2) USE PRIMER EVEN WITH THE HOT BLUE GLUE
07/25/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
- PROVIDE 4" DRYER VENT
- PROVIDE CONDENSATE DRAIN PER PLANS
- PROVIDE MIN. 2" R8 DUCT LINER IN EXPOSED DUCT ON ROOF
- REMOVE TAPE FROM JOINTS ON EXPOSED DUCT
- USE DUCT SEALANT ONLY
- PROVIDE A SERVICE RECEPTACLE ON ROOF