Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* OK FOR SHEETROCK YOU WERE TOLD TO REMOVE ALL TAPE ON EXPOSED DUCT PRIOR TO SEALING JOINTS. NEED TO SEE DUCT LINER IN EXPOSED DUCT ON ROOF. FAILURE TO COMPLY WITH THESE ITEMS WILL RESULT IN A REINSPECTION FEE ON FINAL |
|
| 08/10/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PRIMER IS REQUIRED PRIOR TO GLUING PVC FITTINGS 2) USE PRIMER EVEN WITH THE HOT BLUE GLUE |
|
| 07/25/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - PROVIDE 4" DRYER VENT - PROVIDE CONDENSATE DRAIN PER PLANS - PROVIDE MIN. 2" R8 DUCT LINER IN EXPOSED DUCT ON ROOF - REMOVE TAPE FROM JOINTS ON EXPOSED DUCT - USE DUCT SEALANT ONLY - PROVIDE A SERVICE RECEPTACLE ON ROOF |