Permit: T06CM04584

Parcel: 12416093A

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/04/2007 PLUMBING - FINAL Approved
10/02/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
- I CAN SEE TRACER WIRE AT THE METER SO I WILL APPROVE YARDWATER CLEANOUTS TO BE MADE ACCESSIBLE.
- GREEN SOLVENT CEMENT NOT ALLOWED ON ABS
- GREEN SOLVENT CEMENT NOT ALLOWED FOR PVC
- NO NOTICE IN ELECTRIC SERVICE POWER

MAY NOT BE A COMPLETE LIST
10/01/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. NO INSPECTION HISTORY ON SITE
2. PROVIDE INSPECTION HISTORY FOR YARDWATER PIPING
3. CONTINUED "NOT READY" WILL RESULT IN A
REINSPECTION FEE
09/28/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) YOU ARE REQUIRED TO CALL IN, AND HAVE APPROVED, ALL REQUIRED INSPECTIONS PRIOR TO CALLING FINAL
2) YOU MUST MAKE ALL CORRECTIONS NOTED, AND UNCOVER ALL WORK COVERED WITHOUT APPROVAL
3) CONTRACTOR TO PAY REINSPECTION FEE
03/02/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
02/23/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE REDLINE DRAWING FOR ROUGH-SOIL CHANGES
2. HCS NOT PER PLANS