Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/25/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SMOKE DETECTORS TO CLOSE TO CORNERS |
|
| 07/24/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK UNIT ON SW SIDE COMPLETE INSTALLATION OF BUSHINGS IN METAL STUDS ON SECOND UNIT. |
|
| 07/19/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE APPROVED BUSHINGS WHEN INSTALLING ROMEX THRU METAL STUDS OR BEAMS PER NEC 2. SUPPORT VERTICAL RUNS IN WALLS, CODE REQUIRES SUPPORT WITHIN 12" AT TERMINATION |