Permit: T06CM04584

Parcel: 12416093A

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
07/24/2007 FRAMING Approved IVRS - Inspection :*
07/19/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
NEW REVISION CALL FOR (2) 2X4 @ 16" O.C OVER
LIVING ROOM ONLY NAIL (2) 2X4 JOISTS
TOGETHER W/16d STAGGER @ 12" O.C
PROVIDE ATTIC ACCESS 22" X 30"
05/08/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE REVISION BY DSD CITY OF TUCSON REGARDING INTERIOR JOIST CHANGE TJI FOR 2X4 @ 16" O.C
2. PROVIDE REVISION OR ACCEPTED LETTER FOR
HALLWAY 2'-11' SECTION R311.3 OF IRC CALL FOR MINIMUM WIDTH OF HALLWAY SHALL BE NOT LESS THAN 36" FINISH
3. PROVIDE REVISION FOR CHANGE ON MAIN DOOR PLANS CALL FOR FRENCH DOOR 6" WIDTH INSTEAD 36" WIDTH.
04/23/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
METAL BLDG. DOESN'T MATCH ARCH. PLANS
04/16/2007 FRAMING Partial Approval IVRS - Inspection :*
THIS INSPECTION COVER SHELL BLD. FOR ALL STRUCTURAL MAIN FRAMING
04/13/2007 FRAMING Partial Approval IVRS - Inspection :*
FRAMING PARTIAL APPROVED MUST PROVIDE CONNECTIONS BETWEEN COLUMNS AND RAFTER APPROVED PLANS AND CALC. CALL FOR 8 #12 SCREW ON CONNECTION ABOVE MENTIONED.