Permit: T06CM04569

Parcel: 134232150


Addresses:

518 S LEHIGH DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/20/2009 MECHANICAL - FINAL Approved INSPECTION OF A/C UNITS PERFORMED AND APPROVED IN 2007 BY R FREIDENGER AND D QUINN
08/15/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
15 PSI TEST OK
SHEET METAL PLATFORM NOT ACCEPTABLE.
DOES NOT HAVE ENOUGH SUPPORT
HORIZONTAL SECTION OF CONDENSATE DRAIN DOES NOT HAVE SLOPE.
VENT MUST BE DOWNSTREAM OF THE TRAP.