Permit: T06CM04565

Parcel: 140420740

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM04565

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/13/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
NEED REVISION FOR DELETION OF CAN LTG. SOUTH SOFFIT AREA, SUPPORT MC USING APPROVED METHOD, DO NOT USE GRID WIRES INTENDED FOR GRID SUPPORT
COMPLETE J-BOX MAKE UP

RETURN INSP. CONTR. REQUEST AFTER HRS.
PAID CK#56681 $108.00

ADDRESS SOFFIT LIGHTING FOR HARD LID SOFFIT PRIOR TO FINAL.
12/12/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NO SEISMIC WIRES FOR CAN LTG.
2. OPEN J-BOXES, TERMINATIONS
3. INCOMPLETE CONDUIT RUNS, ALSO, BE SURE TO SUPPORT MC & CONDUIT PER CODE.