Permit: T06CM04556

Parcel: 140420740

Inspection Status: Partial Approval

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
12/06/2006 ELECTRIC - ABOVE CEILING Partial Approval RECESSED CAN LIGHTS NOT INSTALLED WEST SOFFIT AREA
INSTALL PANEL SCHEDULE
AFTER HRS. INSP. CK.#56568
12/06/2006 ELECTRIC - ABOVE CEILING Approved
12/04/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
11/29/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SUPPORT MC CABLE PER CODE WITHIN 12" AT
TERMINATION & AT 6' INTERVALS, PER NEC.
2. OPEN J-BOXES, COMPLETE TERMINATIONS.
3. NO LIGHT FIXTURES IN BAR AREA YET
4. WHEN USING SEISMIC WIRES TO SUPPORT CABLES TIE OFF BOTH ENDS. PER NEC.
11/28/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
11/14/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
J-BOXES HAVE MISSING COVERS OR DEMO IF NOT USED.