Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM04556
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | RECESSED CAN LIGHTS NOT INSTALLED WEST SOFFIT AREA INSTALL PANEL SCHEDULE AFTER HRS. INSP. CK.#56568 |
|
12/06/2006 | ELECTRIC - ABOVE CEILING | Approved | ||
12/04/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
11/29/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT MC CABLE PER CODE WITHIN 12" AT TERMINATION & AT 6' INTERVALS, PER NEC. 2. OPEN J-BOXES, COMPLETE TERMINATIONS. 3. NO LIGHT FIXTURES IN BAR AREA YET 4. WHEN USING SEISMIC WIRES TO SUPPORT CABLES TIE OFF BOTH ENDS. PER NEC. |
|
11/28/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
11/14/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* J-BOXES HAVE MISSING COVERS OR DEMO IF NOT USED. |