Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
Permit Number - T06CM04555
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2006 | MECHANICAL - HOODS | Approved | ||
12/04/2006 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* | |
12/01/2006 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* | |
11/29/2006 | MECHANICAL - HOODS | Denied | IVRS - Inspection : See detailed listing on site.| 999* WELDING FOR JOINTS AND SEAMS IN GREASE DUCT FOR HOOD NEED TO COMPLY WITH IMC 506 DO NOT CALL BEFORE COMPLETE OR A REINSPECTION FEE WILL BE CHARGED. |
|
11/28/2006 | MECHANICAL - HOODS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO COMPLETE WELDS - AS THEY ARE NOW, THEY DO NOT ENCLOSE SEAMS - LIGHT IS COMING THROUGH IMC 506.3.2 2. HAVE HOOD DETAIL ON SITE NEXT INSPECTION. |