Permit: T06CM04554

Parcel: 133146610

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
09/25/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
09/12/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
- BUILDING F EAST OF WILMOT
CONNECTING TO EXISTING PLUMBING AT PUBLIC RESTROOM SEEMS TO BE REASONABLE.
- PLAN WILL HAVE TO BE REVISED TO REFLECT INSTALLATION.

- DOUBLE FIXTURE FITTING REQUIRED FOR DOUBLE FIXTURE CONNECTIONS.
- HORIZONTAL CHANGES OF DIRECTION SHALL BE MADE WITH WYE PATTERN FITTINGS.
- TRAP AND TRAP ARM SHALL BE THE SAME SIZE.