Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM04550
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2007 | ELECTRIC - ABOVE CEILING | Approved | ||
02/08/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DO NOT OCCUPY 2) NO MORE THAN 42 CIRCUITS TO A PANEL BOARD 408.15 3) REVISE CIRCUIT DIRECTORIES 4) WHERE ARE CEILING FANS ON PORCHES PER PLANS ? 5) WHERE ARE POWER POLES AS PER PLANS 6) INSTALL PROJECT TO CHECK CONNECTIONS 7) EXIT LIGHTING TO BE AS PER PLANS ON EM SYSTEM 8) TIGHTEN LOOSE OFFICE FURNITURE CONNECTIONS |
|
02/07/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FINISH VDV CABELING 2) SUPPORT M/C CABLE 330.30 AND 300.11 FOR FLOOR BOXES |
|
02/06/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) TIGHTEN LOOSE FITTINGS OFFICE FURNITURE 2) MAKE-UP POWER POLE 3) SUPPORT M/C CABLE AS PER CODE 4) FINISH SUPPORT FIRE ALARAM CABLE PER 760.6 5) BOXES MORE THAN 1/4" 314.20 6) PANEL BOARD FOR LIGHTING NOT TO HAVE MORE THAN 42 CIRCUITS 7) NED TO INSPECT CORE-THRU FLOOR BOXES WIRING METHODS |
|
01/25/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. CORDS NOT ALLOWED ABOVE CEILINGS 400.7 & 8 |
|
01/05/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection OK TO TILE |
|
01/03/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. FILL UNUSED OPENINGS - NO OLD FITTINGS 110.12 2. SUPPORT WIRES NEED ON CANS, EXIT SIGNS AMENDMENTS 3. HAVE BOX FILL CONCERNS 314.16 4. USE APPROVED STRAPS 110.3 5. FINISH PREVIOUS ITEMS 2, 3 & 6 *BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20 |
|
12/28/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) FINISH PREVIOUS ITEMS |
|
12/21/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. PROPERLY SUPPORT EXIT LIGHT (NORTHWEST) 2. SUPPORT ALL VDV CABELING 725.3 & 6, 800.3 & 6, 300.11 3. FIXTURES TO BE ATTACHED TO GRID 410.16 4. USE APPROVED M/C SUPPORTS FROM BOXES 5. SUPPORT M/C CABLES 12" FROM BOXES AND UPON EXITING WALLS FOR FISHED WIRES. 6. TIGHTEN LOOSE BOX FITTINGS. |