Permit: T06CM04550

Parcel: 12709001E

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM04550

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/23/2007 ELECTRIC - ABOVE CEILING Approved
02/08/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DO NOT OCCUPY
2) NO MORE THAN 42 CIRCUITS TO A PANEL BOARD 408.15
3) REVISE CIRCUIT DIRECTORIES
4) WHERE ARE CEILING FANS ON PORCHES PER PLANS ?
5) WHERE ARE POWER POLES AS PER PLANS
6) INSTALL PROJECT TO CHECK CONNECTIONS
7) EXIT LIGHTING TO BE AS PER PLANS ON EM SYSTEM
8) TIGHTEN LOOSE OFFICE FURNITURE CONNECTIONS
02/07/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) FINISH VDV CABELING
2) SUPPORT M/C CABLE 330.30 AND 300.11 FOR FLOOR BOXES
02/06/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) TIGHTEN LOOSE FITTINGS OFFICE FURNITURE
2) MAKE-UP POWER POLE
3) SUPPORT M/C CABLE AS PER CODE
4) FINISH SUPPORT FIRE ALARAM CABLE PER 760.6
5) BOXES MORE THAN 1/4" 314.20
6) PANEL BOARD FOR LIGHTING NOT TO HAVE MORE THAN 42 CIRCUITS
7) NED TO INSPECT CORE-THRU FLOOR BOXES WIRING METHODS
01/25/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. CORDS NOT ALLOWED ABOVE CEILINGS 400.7 & 8
01/05/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection
OK TO TILE
01/03/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. FILL UNUSED OPENINGS - NO OLD FITTINGS 110.12
2. SUPPORT WIRES NEED ON CANS, EXIT SIGNS AMENDMENTS
3. HAVE BOX FILL CONCERNS 314.16
4. USE APPROVED STRAPS 110.3
5. FINISH PREVIOUS ITEMS 2, 3 & 6

*BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20
12/28/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) FINISH PREVIOUS ITEMS
12/21/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. PROPERLY SUPPORT EXIT LIGHT (NORTHWEST)
2. SUPPORT ALL VDV CABELING 725.3 & 6, 800.3 & 6, 300.11
3. FIXTURES TO BE ATTACHED TO GRID 410.16
4. USE APPROVED M/C SUPPORTS FROM BOXES
5. SUPPORT M/C CABLES 12" FROM BOXES AND UPON EXITING WALLS FOR FISHED WIRES.
6. TIGHTEN LOOSE BOX FITTINGS.