Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/07/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* OK WALLS |
|
| 11/03/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. FILL UNUSED OPENINGS. 2. IS RECEPTACLE HIDDEN IN WALL NOT LIVE 3. SUPPORT VDV CABELING IN WALLS 725.6 & 800.6 4. GROUNDS TO BE FULLY TERMINATED AT SCREWS 5. SUPPORT M/C CABLE IN WALL OFFICE #2 6. TIGHTEN LOOSE FITTINGS. OK WALLS EXCEPT AS NOTED. |